Jog
The jog frequency is immediately output regardless of the predetermined
acceleration time. The jog frequency (JOG) and the type of jog stop pattern
(J.StP) must be pre-selected.
8 - 7
The following table identifies the STOP pattern and the next table illustrates a
JOG RUN in which the parameters "JOG" and "J.Stp" equal 5Hz and 1,
respectively.
6
Jog drive frequency
0 to 20
Hz
5
8-23
Jog stop control
0: Deceleration stop
1: Coast stop
0
8-23
2: DC injection stop
Function Function
Adjustment
Factory
Error
Ref.
No.
Name
Display
Range
Unit
Set
Message
Page
DC injection starting
0.0 to 10
Hz
0
8-27
2ND
frequency
1
DC injection voltage
0 to 20
%
0
8-27
Function Parameters
0
Motor will decelerate to a stop at the rate of DEC1, or DEC2, (dependent upon SEL2).
1
Motor will coast to a stop.
2
Motor will have DC injection applied based upon the DC injection parameters located
in the 2nd Function #1.
Key
Action
Display
The inverter must be placed in the
monitor mode
and stopped before
activating the
jog feature
.
Engages the
jog feature
.
Sets a forward run jog.
Sets a reverse run jog.
When held down the inverter will run at the preset jog speed.
When released the motor coasts to a stop (J.StP=1).
Disables the
jog feature
. The inverter returns to the
monitor mode
.
MON
2ND
0
RUN
RUN
CLR
STOP
or
Pattern
Jogging Stop Pattern
Activating the JOG Feature