8.5.3
Fault-Detection Output Terminals
When any of the inverter's system protection features are activated and the
inverter trips (see list of probable causes in section 7.5.2), the cause of the
problem will be displayed and the fault-detection relay will be activated. This will
cause the contacts associated with the Fault-Detection Output Terminals to
change state. The fault-detection terminals FLA, FLB, and FLC are provided as
a NO, NC form C contact rated for a 250Vac/30Vdc 2A output.
8 - 18
FL
FLC
FLB
FLA
NO
NC
Terminal Connections
Internal To
Inverter
8.5.4
Resetting After a Trip
The inverter can be reset after a trip by two methods:
1)
Pressing the
CLR
and
WRT
keys on the operating panel resets the
inverter locally.
2)
Momentarily closing a normally open contact between terminals
RST
and
COM
resets the inverter remotely.
CAUTION
When the inverter trips due to an emergency stop or the
activation of one or more of its protective functions, the
cause of the fault must be corrected before resetting the
inverter. A forced restart with out prior fault correction
measures could damage the inverter and connected devices.