Operating Functions - Descriptions and Examples (Cont'd)
The following example shows how to
Start-Stop
the unit remotely and have the
frequency
set via the touch-pad. To do this, set the paramenters on
2nd
function
9
as follows.
8 - 30
The inverter must always be placed in the function mode before
accessing any function.
When this key is pressed the inverter is placed into the second
function files.
When this key is pressed the inverter is placed into the second
function file number 9.
When this key is pressed the standard factory adjustment range
setting of 7 is displayed.
When the keys
1
and
WRT
are pressed in order then the factory
adjustment range setting of 1 is written into memory replacing the
factory setting of 7.
When this key is pressed the second menu item under the 2nd 9
functions is displayed.
When this key is pressed the standard factory adjustment range
setting of 7 is displayed.
When the keys
2
and
WRT
are pressed in order then the factory
adjustment range setting of 2 is written into memory replacing the
factory setting of 7.
Returns the inverter to the original monitor mode.
Key
Action
Display
MON
2ND
READ
1
WRT
9
NEXT
READ
WRT
2
MON
In order to run the inverter, simply enter the desired frequency followed by the
WRT
key.
The remote start/stop switch will be put between F (forward) or R (reverse) and CC
terminals on the terminal strip. Closing the connection will make the inverter run,
opening the connection will make the inverter decelerate to a stop at the programmed
deceleration time.