Acceleration time #1
3.0 - 1200 sec
60.0 sec
9-1
2
Deceleration time #1
3.0 - 1200 sec
60.0 sec
9-1
3
Upper frequency limit
0.0 Hz - FH
60.0 Hz
9-1
4
Lower frequency limit
0.0 Hz - UL
0.0 Hz
9-1
5
Terminal IV point #1setting signal
0 - 100 %
20 %
9-1
6
Point #1 output frequency
0.0 Hz - FH
0.0 Hz
9-1
7
Terminal IV point #2 setting signal
0 - 100 %
100 %
9-1
8
Point #2 output frequency
0.0 Hz - FH
60.0 Hz
9-1
9
Electronic thermal protection level
10 - 100 %
100 %
9-1
10
Stall prevention activation level
10 - 115 %
115 %
9-1
11
Electronic thermal protection select
0: STD-motor, no soft stall
0
9-2
1: STD-motor, soft stall
2: VF-motor, no soft stall
3: VF-motot, soft stall
1
Maximum frequency
30 - 120 Hz
60 Hz
9-3
2
Automatic torque boost
0: Off
0
9-3
1: On
3
Torque boost
0 - 30 %
****3 %/1 %
9-3
4
Base frequency of maximum voltage level
30 - 120 Hz
60 Hz
9-3
5
Standard setting mode selection
0: Factory settings
0
9-3
1: 50 Hz motor
2: 60 Hz motor
3: Reset to factory settings
6
Acceleration time #2
3.0 - 1200 sec
10.0 sec
9-3
7
Deceleration time # 2
3.0 - 1200 sec
10.0 sec
9-3
8
Pattern of ACC/DEC #1
0: Linear
0
9-3
1: S-curve
2: C-curve
9
Pattern of ACC/DEC #2
0: Linear
1
9-4
1: S-Curve
2: C-Curve
10
Selection to use ACC/DEC #1 or #2
0: Acc/Dec #1
0
9-4
1: Acc/Dec #2
11
V/F pattern
0: Constant torque
1
9-4
1: Variable torque
12
Timed stop/coast to stop selection
0: Deceleration stop
0
9-4
1: Coast to stop
13
Personal lock out code
0 - 255
0
9-4
7 - 2