System Status Monitoring
The inverter operates with varying levels of supply voltage and current. A variable output
frequency of voltage and current is generated to drive the motor load. These input and output
levels of operating voltage and current are continually monitored by the inverter. It also monitors
for over temperature, input and output terminal settings, and condition of the microprocessor
with associated memory elements. These operating settings and variables have a certain value
or "status" associated with them and are used for inverter operation. They can also be monitored
by the operator to show the setup and conditions existing at any time. Three types of status
monitoring are used and explained below.
8.1
Normal Status Monitoring
Normal status monitoring occurs during normal operation. The ST-CC terminal must be
closed to run. The following table shows applicable keys, display, and status conditions
for normal status monitoring. The display values are for factory settings where no trips
or errors occurred. The display will change only if a new value is programmed into the
associated group adjustment range or if trips or errors have occurred. Scrolling occurs
by repeatedly pressing the READ/WRITE key after output frequency is displayed. Trips
or errors that have occurred (up to a total of four), will be displayed in order immediately
after the keypad software version display.
Key
Display
Status Condition
Inverter is in the off position when ":OFF" is flashing.
Inverter is ready to run from terminal or computer interface.
Inverter is ready to run from keypad and manual control LED
is on.
Displays inverter's output frequency.
Emergency stop executed from keypad while in an automatic
run or while in remote control mode when "E" is flashing.
Indicates a forward (F) or reverse (r) run. If not running,
the display refers to the direction the unit would run.
Displays the frequency which the inverter is set to output
when running (60 Hz is factory setting).
Displays the percentage of the inverter's rated output current
when running (displays "0" when not running).
Displays the percentage of the inverter's rated output voltage
when running (displays "3" when not running).
Displays input terminal status code. See page 8-4
Displays output terminal status code. See page 8-5
Displays inverter's software version.
Displays keypad's software version.
Displays 4th error (no error occurred).
Returns to the original display of output frequency.
8 - 1
OFF
AUTO
MAN
[Output Frequency]
RUN
RD/WRT
RD/WRT
RD/WRT
or
RD/WRT
RD/WRT
RD/WRT
RD/WRT
[Output Frequency]
STOP
RD/WRT
RD/WRT
RD/WRT