Input Terminal Status Code
The table below shows the status codes when contact closures are placed across the
input terminals. JOG(SS2) and AD2(SS3) are multi-functional terminals. The correct
terminal input representation is determined by setting the Input Selection function [:l.tb].
Refer to Item 5 on page 7-3 and Terminal Block details on page 5-3. A reading such as
the example below indicates that terminal ST-CC has a closed contact across it. If input
terminal select [:l.tb]=3 then terminal JOG(SS2)=JOG, terminal AD2(SS3)=AD2, and
they are both open contact.
Display
RR-CC ST-CC
F-CC
R-CC
Display
SS1-CC
JOG-CC
AD2-CC
RST-CC
(SS2)
(SS3)
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON:
Implies a closed contact or short between terminals.
OFF:
Implies an open contact or no connection between terminals.
Terminal
Connections
Inverter's Status when terminal connections are closed (ON).
RR-CC
(See reference signal terminal connections and functions on page 5-4 and 5-5).
ST-CC
RUN ENABLED (
Must be connected to run)
F-CC
FORWARD RUN ENABLED
R-CC
REVERSE RUN ENABLED
If both F-CC and R-CC are on then a REVERSE RUN IS ENABLED.
SS1-CC
MULTI-SPEED RUN ENABLED
SS2-CC
MULTI-SPEED RUN OR JOG RUN ENABLED (Dependent upon SS2's usage)
SS3-CC
MULTI-SPEED RUN OR ACC/DEC 2 ENABLED (Dependent upon SS3's usage)
RST-CC
RESET MODE ENABLED (Reset occurs after momentary contact closure)