10.2
Starting/Stopping-Remote Control
The remote STARTING/STOPPING possibilities are identified in the following
figure and table.
10 - 2
ST
F
R
CC
F
R
ST
Remote START/STOP Connections Possibilities
Terminal Connection
Action
ST-CC
F-CC
R-CC
OFF
ON/OFF
ON/OFF
The inverter is OFF. OFF will be displayed. If running
when ST-CC is broken the motor will coast to a stop.
ON
OFF
OFF
The inverter is ON but not running.
ON
ON
OFF
The inverter is ON and will run in a FORWARD direction if an
input signal is applied.
ON
OFF
ON
The inverter is ON and will run in a REVERSE direction if an
input signal is applied.
ON
ON
ON
Same as REVERSE connection above.
Notes:
1)
With ST-CC (ON), switching F-CC or R-CC (OFF) will cause the motor to decelerate to a stop.
2)
If input power is turned off (with MCCB) while inverter is running, the motor will coast to a stop.
Avoid using the input power switch to start and stop the motor. Use the breaker for an
emergency stop only.
3)
Acceleration and Deceleration rates are determined by the preset values of function [:ACC1],
[:ACC2] and [:DEC1], [:DEC2].
4)
When switching from a forward run to a reverse run the motor will decelerate to a stop then
accelerate in the reverse direction.
10.3
Remote control Frequency Setting
The drive can be run at various frequencies by use of external analog voltage and current
control signals applied to terminals IV and RR. The keypad is not used for this operation
other than assignment of values and programming instructions. It may be desirable from
a security standpoint to disable the touchpad, when programming is completed, so that
customer parameters and programming cannot be changed or revised. Use function
[:RR.cc] item 2 on page 7-5 to set the terminals.
When the IV input is selected, an
auto-mode is in effect so that voltage sensing terminal RR will override current
sensing terminal IV if a voltage is applied to terminal RR. See Terminal/Jumper
Connections for Input Reference Signals chart on page 5-4.
* ON = dry contact closure, OFF = dry contact opening
START/STOP Terminals Connections
(see terminal block detail section 5.6)