Title 

Communi

cation No. 

Function Description 

Factory 

setting



 

0849 

Communication2 time-out 
condition selection 

0: Disconnection detection 
1: When communication mode enabled 
2: 1+Driving operation 

0.0 



 

0850 

Disconnection detection 
extended time 

0.0~100.0 sec. 

0.0 

f851 

0851 

Operation  
at communication error   
by disconnection 

0: Inverter stop, communication command, frequency 

mode open (by 

cmod

fmod

1: None (continued operation) 
2: Deceleration stop 
3: Coast stop 
4: Network error (

err8

 trip) 

5: Preset speed operation (by 

f852

 setting) 

f852 

0852 

Preset speed operation 
selection 

0:None 
1~15:Preset speed operation (by parameter setting) 

f831-

f838 

0831- 

0838 

IO Scanner   
Command data

 

0: No action 
1: FA06 (Communication option command 1) 
2: FA23 (Communication option command 2) 

3: FA07 (Frequency command, 0.01Hz) 

4: FA33 (Torque command, 0.01%) 
5: FA50 (Terminal output data from comm.) 
6: FA51 (Analog output (FM) data from comm.) 
7: FA52 (Analog output (AM) data from comm.) 
8: F601 (Stall prevention level, %) 
9: F441 (Power running torque limit 1 level, 0.01%) 

10: F443 (Regenerative braking torque limit 1 level, 

0.01%) 

11: F460 (Speed loop proportional gain) 
12: F461 (Speed loop stabilization coefficient) 

f841- 

f848 

0841- 

0848 

IO Scanner   
Monitor data

 

0: No action 
1: FD01 (Inverter status 1) 
2: FD00 (Output frequency, 0.01Hz) 
3: FD03 (Output current, 0.01%) 
4: FD05 (Output voltage, 0.01%) 
5: FC91 (Inverter alarm) 
6: FD22 (PID feedback value, 0.01Hz) 
7: FD06 (Input terminal status) 
8: FD07 (Output terminal status) 
9: FE36 (VI/II input, 0.01%) 

10: FE35 (RR/S4 input, 0.01%) 
11: FE37 (RX input, 0.01%) 
12: FD04 (Input voltage (DC detection), 0.01%) 
13: FD16 (Speed feedback (real-time value), 0.01Hz) 
14: FD18 (Torque, 0.01%) 
15: FE60 (My monitor) 
16: FE61 (My monitor) 
17: FE62 (My monitor) 
18: FE63 (My monitor) 
19: F880 (Free notes) 
20: FD29 (Input power, 0.01kW) 
21: FD30 (Output power, 0.01kW) 
22: FE14 (Cumulative operation time, 0.01=1 hour) 
23: FE40 (FM terminal output monitor) 
24: FE41 (AM terminal output monitor) 

f899 

0899 

Network option reset 
setting 

0:None 
1:Reset option circuit board and inverter 

FE66 

Add-on option 1 CPU 
version (Under side option)

FE67 

Add-on option 2 CPU 
version (Panel side)

 

High byte is version. Low byte is revision. 
For example, When version number 1, and revision 
number 2 is, panel indication becomes with 1.02. 
  The version of the option with it has equipped can be 
checked by using the function of 

f710

 to 

f718

 

(standard monitor display selection). 

*For details, refer to the inverter instruction manual. 

(*1): This parameter is effective by reset. Please reset (power supply reset or 

f899

=

1

) after changing a set point. 

(*2): The factory default setting parameter (



) does not work for this parameter.   

- 11 - 

Summary of Contents for TOSVERT IPE001Z

Page 1: ... are subject to change without notice Please confirm the latest information on our web site www inverter co jp 2 Read this manual before installing or operating the EtherNet IP option unit Keep it in a safe place for reference 1 Make sure that this instruction manual is delivered to the end user of EtherNet IP option unit NOTICE ...

Page 2: ...hat errors in operation may lead to injury 1 to people or that these errors may cause damage to physical property 2 1 Such things as injury burns or shock that will not require hospitalization or long periods of outpatient treatment 2 Physical property damage refers to wide ranging damage to assets and materials Meanings of symbols Marking Meaning of marking Indicates prohibition Do not do it What...

Page 3: ...Do not touch the sharp portions such as leads of parts on the board the corner of board or etc on this option It may lead to injuries Caution Mandatory This option is an electrostatic discharge sensitive device Handle it where the environment is protected against electrostatic electricity Otherwise permanent damage to device will result Transportation and installation Warning Prohibited Do not app...

Page 4: ...rror power outage failure etc Network time out f850 See the VF AS1 PS1 EtherNet IP Communication Function Manual for details Deactivated option unit may cause an accident if the Communication error trip function is not properly set up Make sure that the operation signals are STOP before resetting inverter s fault The motor may suddenly start and that may result in injuries Disposal Caution Mandato...

Page 5: ... sales offices or web site www inverter co jp EtherNet IP option Function Manual E6581581 After reading this instruction manual please keep it handy for future reference EtherNet IP is a trademark of ControlNet International Ltd IPE001Z is applicable for VF AS1 software version V150 or later and VF PS1 software version V650 or later Part numbering IPE 001 Z 0 Revision number Cable length Z means w...

Page 6: ...n layout 7 2 3 Example of connection to an EtherNet IP 7 2 4 LED indicator 8 3 Installing the IPE001Z 9 4 Parameters 10 4 1 Communication parameters 10 4 2 f851 Communication Loss Action Setting Network Disconnection 12 5 Command Setpoint selection Local Remote 13 6 Specifications 15 7 Warranty 15 5 ...

Page 7: ...et IP network 2 Names and functions The drawing below shows names and functions of main parts 2 1 Outline Connector to the inverter Label MAC address Port R EtherNet IP Connector Shielded female RJ45 Earth Plate Panel mounting tabs EtherNet IP LED indicator See 2 4 Port L EtherNet IP Connector Shielded female RJ45 6 ...

Page 8: ... Mbps Pin Signal 1 TD 2 TD 3 RD 4 5 6 RD 7 8 Fix a cable so that a communication connector may be not taken the weight of wire 2 3 Example of connection to an EtherNet IP Daisy chain and or star topology Notes Provide strain relief so that the communication connector does not take the weight of the cable Please connect this option to only the Modbus TCP communication line This option does not work...

Page 9: ... 2 3 Link Green flashing 5 times The card is performing a BOOTP or DHCP sequence OFF The device does not have an IP address or powered off Flashing Green Red Power up testing Green ON The device has at least one established connection even to the Message Router Green flashing The device has not established connections but has obtained an IP address Red flashing One or more of the connections in wh...

Page 10: ... panel cover b Install the option in the inverter by fitting the tabs on the lower side the option into the slots at the lower part of the inverter front panel 1 c Make sure the option is securely attached to the inverter Then check whether the plastic bosses on the inverter case have fitted in the holes at the upper and lower parts of the option d Insert the tabs at the lower part of the front co...

Page 11: ...99 DEVICE NAME 1 16 characters by a hex digit 0h to FFFFh for each of fields There are 2 characters per one parameter The device name is required if the card uses DHCP to obtain its IP Address 0 0 0 0 0 0 0 0 HEX 2 f576 0576 IP mode 1 Use this parameter to select the IP address assignment method 0 Manual 1 BOOTP 2 DHCP 0 f577 f580 0577 0580 IP address 1 IP address of the card 0 to 255 for each of ...

Page 12: ...nitor data 0 No action 1 FD01 Inverter status 1 2 FD00 Output frequency 0 01Hz 3 FD03 Output current 0 01 4 FD05 Output voltage 0 01 5 FC91 Inverter alarm 6 FD22 PID feedback value 0 01Hz 7 FD06 Input terminal status 8 FD07 Output terminal status 9 FE36 VI II input 0 01 10 FE35 RR S4 input 0 01 11 FE37 RX input 0 01 12 FD04 Input voltage DC detection 0 01 13 FD16 Speed feedback real time value 0 0...

Page 13: ... not canceled 4 Emergency stop The error message err8 is displayed Commands entered through the network are not canceled When communications are restored the inverter is not restored to working order and the error message err8 does not disappear until the inverter is reset 5 Preset speed operation command The drive will run at a preset speed as set up by f852 in the case of a communication loss wi...

Page 14: ...truction manual for the parameter in detail Command Setpoint Operation Panel EASY key f750 2 Local Remote key Logic input 48 SC LC Network cancel switch Network EtherNet IP Network EtherNet IP 0 1 ON OFF 0 1 Operation Panel ON OFF Control Terminal VI Control Terminal RR Operation Panel Network EtherNet IP fmod 1 2 4 7 Control Terminal Operation Panel Network EtherNet IP cmod 0 1 4 Remote Local Rem...

Page 15: ...minal board fmod Frequency setting mode selection 1 2 RR S4 f112 Input terminal selection 2 R 48 Remote Local control Operation R CC terminal open VF AS1 PS1 is controlled as a slave device of The EtherNet IP R CC terminal closed F CC terminal short to RUN F CC terminal open to STOP Output frequency is set up by the RR S4 signal input Note When the local HAND remote key f750 2 is chosen as EASY ke...

Page 16: ...lve months from the date of delivery shall be repaired free of charge 3 For the following kinds of failure or damage the repair cost shall be borne by the customer even within the warranty period i Failure or damage caused by improper or incorrect use or handling or unauthorized repair or modification of the option ii Failure or damage caused by falling or an accident during transportation after t...

Reviews: