E6581090
I-7
9
Table 4. AIC and fuse
Voltage class
Capacity of
applicable motor
(kW)
Inverter model
AIC
(Interrupting
capacity
)
Fuse class and
currents
(
A
)
0.1
VFNC1S-1001P
AIC 1000A
CC/J 6 max
0.2
VFNC1S-1002P
AIC 1000A
CC/J 8 max
0.4
VFNC1S-1004P
AIC 1000A
CC/J 12 max
Single-phase
100V class
0.75
VFNC1S-1007P
AIC 1000A
CC/J 22 max
0.2
VFNC1S-2002P(L)
AIC 1000A
CC/J 4 max
0.4
VFNC1S-2004P(L)
AIC 1000A
CC/J 8 max
0.75
VFNC1S-2007P(L)
AIC 1000A
CC/J 12 max
1.5
VFNC1S-2015P(L)
AIC 5000A
CC/J 22 max
Single-phase
200V class
2.2
VFNC1S-2022P(L)
AIC 5000A
CC/J 30 max
0.1
VFNC1-2001P
AIC 1000A
CC/J 3 max
0.2
VFNC1-2002P
AIC 1000A
CC/J 3 max
0.4
VFNC1-2004P
AIC 1000A
CC/J 5 max
0.75
VFNC1-2007P
AIC 1000A
CC/J 8 max
1.5
VFNC1-2015P
AIC 5000A
CC/J 15 max
Three-phase
200V class
2.2
VFNC1-2022P
AIC 5000A
CC/J 20 max
9.2.4 Motor thermal protection
Selects the electronic thermal protection characteristics that fit with the ratings and characteristics
of the motor. In case of multi motor operation with one inverter, thermal relay should be connected
to each motor.