E6581090
K-2
11
Title
Communication
No.
Function
Unit
Minimum setting
unit Panel/
Communication
Adjustment range
Default
setting
User
setting
Reference
V[R
0007
Standard setting mode
selection
-
-
0:-
1:Set at 50Hz
2:Set at 60Hz
3:Default setting
4:Trip clear
5:Cumulative
operation time clear
0
5.3
HT
0008
Forward/reverse
selection (Operation
panel)
-
-
0:Forward run
1:Reverse run
0
5.4
CEE
0009
Acceleration time 1
s
0.1/0.1
0.1-3000
10.0
5.5
FGE
0010
Deceleration time 1
s
0.1/0.1
0.1-3000
10.0
5.5
HJ
0011
Maximum frequency
Hz
0.1/0.01
30.0-200
*2
5.6
WN
0012
Upper limit frequency
Hz
0.1/0.01
0.5-
HJ
*2
5.7
NN
0013
Lower limit frequency
Hz
0.1/0.01
0.0-
WN
0.0
5.7
XN
0014
Base frequency 1
Hz
0.1/0.01
25-200
*2
5.8
RV
0015
V/F control mode
selection
-
-
0 (1, 2): V/F
3: Sensorless vector
control
0
5.9
XD
0016
Torque boost 1
%
0.1/0.1
0.0-30.0
*3
5.9
VJT
0600
Motor thermal
protection level 1
%
1/1
30-100
100
5.10
QNO
0017
Electronic thermal
protection
characteristic *4
-
-
0
5.10
UT
0018
Preset speed operation
frequencies 1
Hz
0.1/0.01
NNWN
0.0
UT
0019
Preset speed operation
frequencies 2
Hz
0.1/0.01
NNWN
0.0
UT
0020
Preset speed operation
frequencies 3
Hz
0.1/0.01
NNWN
0.0
UT
0021
Preset speed operation
frequencies 4
Hz
0.1/0.01
NNWN
0.0
UT
0022
Preset speed operation
frequencies 5
Hz
0.1/0.01
NNWN
0.0
UT
0023
Preset speed operation
frequencies 6
Hz
0.1/0.01
NNWN
0.0
UT
0024
Preset speed operation
frequencies 7
Hz
0.1/0.01
NNWN
0.0
5.11
H
-
Extended parameter
-
-
-
-
-
4.1.2
ITW
-
Search for changed
settings
-
-
-
-
-
4.1.3
*2: The value is changed according to the set-up parameter condition.
(VFNC1 (S)-
□□□□
P
□
-W type)
FH:80, UL80, VL:60, F127:0, F170:60, F171:200, F204:80, F409:200, F417:1710 for VFNC1 (S)-
□□□
□
P
□
type.
*3: Parameter values vary depending on the capacity. Refer to page K-8.
*4:
○
: Applicable,
×
: Inapplicable
Se
tti
ng
Ov
e
rlo
a
d
protec
tio
n
Ov
e
rlo
a
d
st
a
ll
0
○
×
1
○
○
2
×
×
3
St
andar
d
mo
to
r
×
○
4
○
×
5
○
○
6
×
×
7
VF
m
otor
×
○