11
•
Operation mode parameters
Title
Communication
No.
Function
Unit
Minimum setting unit
Panel/
Communication
Adjustment range
Default
setting
User
setting
Reference
H
0300
PWM carrier
frequency
-
-
0:2kHz
1:2kHz (Random
mode)
2:4kHz
3:4kHz (Random
mode)
4:8kHz
(
auto-reduction
mode
)
5:12kHz (auto-
reduction mode)
6:16kHz (auto-
reduction mode)
5
6.9
H
0301
Auto-restart control
selection
-
-
0:Disabled
1:At auto-restart after
momentary stop
2:When turning ST-
CC on or off
3:At auto-restart after
momentary stop or
when turning ST-CC
on or off
0
6.10.1
H
0302
Regenerative power
ride-though control
-
-
0:Disabled
1:Enabled
2:Deceleration stop
0
6.10.2
H
0303
Retry selection
(Number of times)
Times
1/1
0(OFF),1-10
0
6.10.3
H
0305
Over voltage limit
operation
-
-
0:Disabled
1:Enabled
2:Enabled (forced
shortened
deceleration)
0
6.10.4
H
0360
PI control
-
-
0: Disabled
1: Enabled
0
6.11
H
0362
Proportional (P) gain
-
0.01/0.01
0.01-100.0
0.30
6.11
H
0363
Integral (I) gain
-
0.01/0.01
0.01-100.0
0.20
6.11
•
Torque boost parameters
Title
Communication
No.
Function
Unit
Minimum setting
unit Panel/
Communication
Adjustment range
Default
setting
User
setting
Reference
H
0401
Slip frequency gain
%
1/1
0-150
50
6.12.1
H
0409
Base frequency
voltage 1
V
1/0.1
50-500
*2
6.12.1
H
0415
Motor rated current
A
0.1/0.1
0.1-50.0
*3
6.12.2
H
0416
Motor no-load current
%
1/1
30-80
*3
6.12.2
H
0417
Motor rated speed
min
-1
1/1
100-12000
*2
6.12.2
H
0418
Speed control gain
%
1/1
0-100
40
6.12.2
H
0419
Speed control stable
coefficient
%
1/1
0-100
20
6.12.2
*2: The value is changed according to the set-up parameter condition.
(VFNC1 (S)-
□□□□
P
□
-W type)
FH:80, UL80, VL:60, F127:0, F170:60, F171:200, F204:80, F409:200, F417:1710 for VFNC1 (S)-
□□□
□
P
□
type.
*3: Parameter values vary depending on the capacity. Refer to page K-8.