E6581090
K-6
11
•
Acceleration/deceleration time parameters
Title
Communication
No.
Function
Unit
Minimum setting
unit Panel/
Communication
Adjustment range
Default
setting
User
setting
Reference
H
0500
Acceleration time 2
s
0.1/0.1
0.1-3000
10.0
6.13
H
0501
Deceleration time 2
s
0.1/0.1
0.1-3000
10.0
6.13
H
0505
Acceleration/decelerat
ion 1 and 2 switching
frequency
Hz
0.1/0.01
0-
WN
0.0
6.13
•
Protection parameters
Title
Communication
No.
Function
Unit
Minimum setting
unit Panel/
Communication
Adjustment range
Default
setting
User
setting
Reference
H
0601
Stall prevention level
%
1/1
30-199 (%)
200 (disabled)
150
6.14.1
H
0602
Inverter trip retention
selection
-
-
0: Not retained,
1: Retained
0
6.14.2
H
0603
External input trip stop
mode selection
-
-
0:Coast stop
1:Slowdown stop
2:Emergency DC
braking
0
6.14.3
H
0605
Output phase failure
detection mode
selection
-
-
0:Disabled
1:Selected (Output
open-phase is
checked when
operation is started
for the first time after
power is turned on.)
2:Selected (Output
open-phase is
checked each time
operation is started.)
0
6.14.4
H
0607
Motor 150%-overload
time limit
s
1/1
10
~
800
300
6.14.5
H
0608
Input phase failure
detection mode
selection
-
-
0: Disabled,
1: Enabled
1
6.14.6
H
0616
Over-torque alarm
level
%
1
0-200
150
6.14.7
H
0618
Over-torque detection
time
s
0.1
0.0-10.0
0.5
6.14.7
H
0627
Under voltage trip
selection
-
-
0:Disabled
1:Enabled (64% or
less: Trip, FL relay
activated)
2:Disabled (50% or
less: Trip, FL relay
not activated)
0
6.14.8
H
0633
Analog input
disconnection
detection
%
1
0 (Disabled), 1 - 100%
0
6.14.9