E6581090
B-8
2
FL
A
FL
B
FL
C
CC
CC
CC
S2
R
S1
F
P5
FM
/O
UT
VI
/S3
P1
5
2.3.2 Control circuit terminals (sink logic (common: CC))
The control circuit terminal board is the same for all models.
Termina
l symbol
Input/
output
Function
Specifications
Inverter internal circuit
F
Input
Shorting across F-CC
causes forward rotation;
open causes slowdown and
stop. (If ST is always ON)
R
Input
Shorting across R-CC
causes reverse rotation;
open causes slowdown and
stop. (If ST is always ON)
Shorting across R-CC/F-
CC causes reverse
rotation.
S1
Input
Shorting across S1-CC
causes preset speed
operation.
S2
Input
Mu
lti
fu
nc
tio
n progra
mmabl
e
co
nt
ac
t i
np
ut
Shorting across S2-CC
causes preset speed
operation.
Dry contact input
15Vdc - 5mA or less
*Sink/source selectable
by changing a parameter
CC
Common
to input/
output
Control circuit’s equipotential
terminal.
P5
Output Power output for analog input
setting.
5Vdc
(permissible load current:
10mAdc)
VI/S3
Input
Multifunction programmable
analog input.
Standard default setting:
Analog input 0-10Vdc and
frequency 0-80Hz.
Possible to use as analog input
(4 (0)-20mAdc) or contact input
(programmable contact input)
by changing a parameter.
10Vdc:
(internal impedance:
42k
Ω
)
4-20mA:
(internal impedance:
250
Ω
)
◎
4.7K
3.7K
+5V
22K
1K
0.047μ
+15V
F
S
2
~
◎
CC
◎
249
+5V
20K
2K
0.047μ
VI/S3
0.047μ
20K
◎
100
P5
+5V