E6581090
E-3
5
■
Adjustment scale with meter adjustment
HO
parameter
Connect meters as shown below.
FM/OUT
CC
Meter: frequency
meter
(default setting)
VF-nC1
The reading of the frequency
meter will fluctuate during
scale adjustment.
Meter: ammeter
(
HOUN
: 1)
The reading of the frequency
meter will fluctuate during
scale adjustment.
+
-
㧗
-
☆
Optional frequency meter: QS-60T
☆
Make the maximum ammeter scale at least 150
percent of the inverter's rated output current.
<Frequency meter>
<Ammeter>
FM/OUT
CC
VF-nC1
[Connected meter selection parameters]
Title
Function
Adjustment range
Default setting
HOUN
Meter selection
-1 : Open collector output
0 : Output frequency
1 : Output current
2 : Set frequency
3 : For adjustment (current fixed at 100%)
4 : For adjustment (current fixed at 50%)
5 : For adjustment (output fixed at the max
frequency)
6 : For adjustment (gain display )
0
■
Resolution
All FM terminals have a maximum of 1/256
[Example of how to adjustment the FM terminal frequency meter]
* Use the meter's adjustment screw to pre-adjust zero-point.
Key operated
LED display
Operation
–
Displays the operation frequency. (When standard monitor
display selection
H
is set to
[operation frequency])
CWJ
The first basic parameter "
CWJ
" is displayed.
HO
Press either the
△
key or the
▽
key to select "
HO
."
Press the ENTER key to confirm your choice. A value
corresponding to the setting of
HOUN
(FM/OUT terminal
functions selection) is displayed.
Press the
△
key or the
▽
key to adjust the meter. The
meter reading will change at this time but be careful
because there will be no change in the inverter's digital LED
(monitor) indication.
⇔
HO
The adjustment is complete.
HO
and the frequency are
displayed alternately.
The display returns to its original indications (displaying the
operation frequency). (When standard monitor display
selection
H
is set to
[operation frequency].)
■
Adjusting the meter in inverter stop state
If, when adjusting the meter for output current, there are large fluctuations in data during
adjustment, making adjustment difficult, the meter can be adjusted in inverter stop state.
If
HOUN
is set to
“for adjustment (current fixed at 100%)”, the inverter puts out signals via the
FM / OUT terminal, assuming that 100% of current (inverter’s rated current) is flowing. In this
state, adjust the meter with the
HO
(Meter adjustment) parameter. (
HOUN
: 4, 5, 6, 7 can be
adjusted in the same way.)
After meter adjustment is ended, set
HOUN
to
(output current).
[Hint]
It's easier to make the
adjustment if you push and
hold for several seconds.
▲
▼
MON
ENT
▲
▼
ENT
MON
MON