E6581090
F-3
6
•
Function
This parameter is used to switch the function of the VI/S3 terminal between analog signal input
and contact signal input.
•
Function
This parameter allows you to select a function you want to keep always active (ON). (Only one
function can be selected.)
Specified frequency reach signal: 8
FM/OUT terminal (
H
)
FL terminal (
H
)
Output frequency [Hz]
Time [sec]
H
-
2.5Hz
ON
OFF
H
+
2.5Hz
H
ON
OFF
0
Specified frequency reach reverse signal: 9
FM/OUT terminal (
H
)
FL terminal (
H
)
* FM/OUT terminal function selection (
HOUN
) : 0 (Output frequency)
Note: Activate
H
to output signals to the FM/OUT terminal, or set
H
to 8 or 9 to output
signals to the FLA, FLC and FLB terminals.
6.2
Parameters related to terminal function selection
6.2.1 Changing the function of the VI/S3 terminal
H
: Analog input/logic input function selection
■
Parameter setting
Title
Function
Adjustment range
Default setting
H
Analog input/logic
input function
selection
0: Voltage signal, 1: Current signal,
2: Contact input
0
* To use the VI/S3 terminal as a contact input terminal in sink connection, be sure to insert an
adequate resistor* between P15 and VI/S3. (* Recommended resistance: 4.7 k
Ω
-1/4W)
6.2.2 Keeping an input terminal function always active
H
: Always active function selection (ST)
■
Parameter setting
Title
Function
Adjustment range
Default setting
H
Always active function
selection (ST)
0~40, 49, 54~57 (See Section 11.)
1 (ST)
6.2.3 Changing the function of an input terminal
H
: Input terminal selection 1 (F)
H
: Input terminal selection 2 (R)
H
: Input terminal selection 3 (S1)
H
: Input terminal selection 4 (S2)
H
: Analog input/logic input function selection *1
H
: Input terminal selection 5 (VI/S3)