E6581090
F-10
6
6.5
Operation frequency
6.5.1 Starting frequency
H
: Starting frequency setting (Hz)
•
Function
The frequency set with the
H
parameter is put out immediately after the completion of
frequency setting.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Starting frequency setting (Hz) 0.5
~
10.0(Hz)
0.5
Starting frequency setting
H
Output frequency [Hz]
Time [sec]
0
6.5.2 Start/stop control by means of frequency setting signals
H
: Operation starting frequency (Hz)
H
: Operation starting frequency hysteresis (Hz)
•
Function
The start/stop of operation can be controlled, by simply using frequency setting signals.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Operation starting frequency
(Hz)
0.0
~
HJ
(Hz)
0.0
H
Operation starting frequency
hysteresis (Hz)
0.0
~
HJ
(Hz)
0.0
0
A
B
100%
Frequency command value
H
+
H
H
H
-
H
HJ
The inverter starts to accelerate when the
frequency setting signal reaches point B.
Deceleration starts when the frequency
setting signal falls below point A.
Output frequency [Hz]