E6581090
F-11
6
6.6
DC braking
6.6.1 DC braking
H
: DC braking starting frequency (Hz)
H
: DC braking current (%)
H
: DC braking time (s)
•
Function
Large braking torque can be obtained by applying a direct current to the motor. These
parameters are used to set the direct current to be applied to the motor, the application time
and the starting frequency.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
DC braking starting frequency
(Hz)
0.0:(OFF),
0.1
~
HJ
(Hz)
0.0
H
DC braking current (%)
0
~
100(%)
50.0
H
DC braking time (s)
0.0:(OFF)
0.1
~
20.0(sec)
1.0
Time [sec]
DC braking starting
frequency
H
DC braking current
H
DC braking time
H
Output frequency [Hz]
DC braking stop
Operation signal [F-CC]
ON
OFF
Output current [A]
0
0
Set frequency
Note: During DC braking, the overload protection sensitivity of the motor increases. To prevent
tripping, the DC braking current is adjusted automatically in some cases.