E6581090
F-26
6
6.14.9 Analog input disconnection detection
H
: Analog input disconnection detection
•
Function
This parameter is used to detect a break in an analog signal to the VI/S3 terminal. If an analog
signal is below the level set with
H
for 0.3 seconds (approx.), the inverter will assume the
signal to be broken and it will trip and display the error message “
G
.” (The Analog input
disconnection detection function is disabled if
H
is set to 0.0%.)
Title
Function
Adjustment range
Default setting
H
Analog input
disconnection detection
0: Disabled
1~100%
0
6.15
Operation panel parameters
6.15.1 Prohibiting the change of parameter settings
H
:
Prohibition of change of parameter settings
•
Function
This parameter specifies whether parameter setting is changeable or not.
■
Setting methods
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Prohibition of
change parameter
settings
0~7 (See the explanation below.)
: Permitted _____
EOQF
and
HOQF
settings cannot be changed during operation. (Default)
: Prohibited _____ All parameters are read/write-protected.
: Permitted _____
EOQF
and
HOQF
settings also can be changed during operation.
: Prohibited _____ Frequency can be changed from the operation panel but all other
parameters are read/write-protected.
: Permitted _____ The emergency stop function cannot be controlled from the operation panel
and
EOQF
and
HOQF
settings cannot be changed during operation.
: Prohibited _____ The emergency stop function cannot be controlled from the operation panel
but all parameters are read/write-protected.
: Permitted _____ The emergency stop function cannot be controlled from the operation panel
and
EOQF
and
HOQF
settings also can be changed during operation.
: Prohibited _____ The emergency stop function cannot be controlled from the operation panel,
frequency can be changed on the operation panel, but any other parameters
are write/read-protected.
Note: Some parameters cannot be changed during operation, no matter how
H
is set. (See
4.1.4.)
■
Canceling the setting
Only the setting of
H
can be changed anytime, no matter how it is set.