E6581595
F-2
6
FLA
FLC
FLB
RY
+24V
An example of the connection of the open collector
OUT terminal (sink logic)
An example of the connection of the relay
output terminals
Output terminal setting
Default outputs low-speed signal (ON signal) to OUT terminal. This setting must be changed to invert
the polarity of the signal.
[Parameter setting]
Title
Function
Adjustment range
Default setting
Output terminal selection 1A (OUT)
0-255
(Refer to section 11.7)
4:
LOW (Low-
speed detection
signal)
Setting value 5 is reverse signal.
Set
to output to FLA-FLC-FLB terminals.
6.1.2
Output of designated frequency reach signal
: Speed reach detection band
Function
When
the output frequency becomes equal to the setting by designated frequency
, an ON
or OFF signal is generated.
[Parameter setting]
Parameter setting of designated frequency and detection band
Title
Function
Adjustment range
Default setting
Speed reach detection band
0.0 -
(Hz)
2.5
Parameter setting of output terminal selection
Title Function Adjustment
range
Setting
Output terminal
selection 1A
(OUT)
0-255
(Refer to section 11.7.)
6: RCH (Output frequency attainment signal
(acceleration/deceleration completed))
Setting value 7 is reverse signal.
Note: Set
to output to FLA-FLC-FLB terminals.
+24V
OUT
NO
CC
Ry
P24