E6581595
F-13
6
1) 0-10Vdc voltage input adjustment
2) 4-20mAdc current input adjustment
3) 0-5 Vdc voltage input, or used to adjust external volume (P5-VI-CC)
VI terminal
Point settings adjust the frequency
command for the current input.
Ramp and bias can be easily set.
With a current input of 0 to 20 mA,
set
f201
to
.
100 (%)
20mA current signal
0 ( Hz)
20 (%)
4
50/60 (Hz)
Frequency commnd
(Current input: 4-20 mA)
VI terminal
Point settings adjust the
frequency command for the
voltage input.
Gradient and bias can be set
easily.
100 (%)
10V voltage signal
0 ( Hz)
0 (%)
0
50/60 (Hz)
Frequency commnd
(Voltage input: 0-10V)
VI terminal
* When the external potentiometer is used, it is so that the frequency set in
output. In case of the
voltage signal 0-5Vdc, when output frequency does not match the value set in
, please adjust
or
(Refer to section 6.5.4 for details).
Point settings adjust the
frequency command for
the voltage input.
Ramp and bias can be
easily set.
100(%)
5V voltage signal
0( Hz)
0(%)
0V
f204
50/60 (Hz)
(Voltage input: 0-5V)