6.5.3 Setting of frequency with the input from an external logic
: External logic input - UP response time
: External logic input - UP frequency steps
: External logic input - DOWN response time
: External logic input - DOWN frequency steps
: Initial value of UP/DOWN frequency
: Change of the initial value of UP/DOWN frequency
Function
These parameters are used to set an output frequency by means of a signal from an external device.
[Parameter setting]
Title
Function
Adjustment range
Default setting
External logic input - UP response
time
0.0 - 10.0 (S)
0.1
External logic input - UP frequency
steps
0.0 -
(Hz)
0.1
External logic input - DOWN response
time
0.0 - 10.0 (S)
0.1
External logic input - DOWN frequency
steps
0.0 -
(Hz)
0.1
Initial value of UP/DOWN frequency
-
(Hz)
0.0
Change of the initial value of
UP/DOWN frequency
0: Not changed
1: Setting of
changed
when power is turned off
1
This function is valid when the parameter
(frequency setting mode selection) =
is set.
■
Input terminal settings
Assign the following functions to the input terminal, you can change (up/down) or clear the output frequency
by using the terminal's ON/OFF.
Input terminal function
ON
OFF
88
Frequency UP
Frequency setting increase
Clear
90
Frequency DOWN
Frequency setting decrease
Clear
92 Clear
frequency
UP/DOWN
OFF
ON: External logic up/down
frequency Clear settings
settings
Each of the following numbers (89, 91, 93) are reverse signals.