E6581595
F-18
6
Starting frequency
Output frequency (Hz)
0
Operation signal (F-CC)
Time
ON
OFF
6.6 Operation
frequency
6.6.1 Starting
frequency
: Starting frequency
Function
The frequency set with
is put out as soon as operation is started.
Use the
parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title
Function
Adjustment range
Default setting
Starting frequency
0.1-10.0 (Hz)
0.5
6.6.2
Run/stop control with frequency setting signals
: Operation starting frequency
: Operation starting frequency hysteresis
Function
The Run/stop of operation can be controlled simply with frequency setting signals.
[Parameter setting]
Title Function
Adjustment range
Default setting
Operation starting frequency
0.0-
(Hz)
0.0
Operation starting frequency hysteresis
0.0-
(Hz)
0.0
0
A
B
100% Frequency command value
+
-
When the frequency command signal
reaches the B point, the inverter
operates.
When decelerating, operation stops
when the frequency setting signal is less
than point A.
Output frequency [Hz]