E6581595
F-25
6
2) Restarting motor during coasting (Motor speed search function)
Motor speed
Forward / reverse
ON
OFF
ST-CC
ON
OFF
Setting
to
or
: This function operates after the ST-CC terminal connection has been opened
first and then connected again.
Note 1: The terminal function ST needs to be assigned to an input terminal, using the parameters
to
.
3) Motor speed search at starting
When
is set to
, a motor speed search is performed each time operation is started.
This function is useful especially when the motor is not operated by the inverter but it is running because of
external force.
Warning!!
At restart, it takes about 1 second for the inverter to check to see the number of revolutions of the
motor.
For this reason, the start-up takes more time than usual.
Use this function when operating a system with one motor connected to one inverter.
This function may not operate properly in a system configuration with multiple motors connected to
one inverter.
In case of using this function, do not set the output phase failure detection selection
(
f605
=
1
,
2
).
Application to a crane or hoist
The crane or hoist may have its load moved downward during the above
waiting time from input of the operation starting command to the restart of the
motor. To apply the inverter to such machines, therefore, set the auto-restart
control mode selection parameter to "
=
" (Disabled), Do not use the
retry function, either.
Note 2: It is not malfunction that abnormal noise might be heard from the motor during the motor speed
search at the auto-restart.