E6581595
F-48
6
[Parameter setting]
Title
Function
Adjustment range
Default setting
Small current detection hysteresis
1-20 (%)
10
Small current trip/alarm selection
0: Alarm only
1: Tripping
0
Small current detection current
0-150 (%) / (A)
0
Small current detection time
0-255 (s)
0
<Example of operation>
Output terminal function: 26 (UC) Low current detection
f610
=
0
(Alarm only)
Time [sec]
+
Output current (%)
Low current
signal output
or less
ON
OFF
OFF
* When
setting
f610
to
1
(Trip), trip after low current detection time setting of
f612
. After tripping,
the low current signal remains ON.
6.16.8 Detection of output short-circuit
: Detection of output short-circuit at start-up
Function
This parameter detects inverter output short-circuit. It can be usually detected in the length of the
standard pulse. When operating low-impedance motor such as high-speed motor, however, select the
short-time pulse.
=
: Detection is executed in the length of the standard pulse every time you start up the inverter.
=
: Detection is executed in the length of standard pulse only during the first start-up after putting on
the power or after resetting.
=
: Detection is executed with the short-time pulse every time you start up the inverter.
=
: Detection is executed with the short-time pulse only for the first time after putting power on or
after resetting.