6.17.2 Calibration of analog output
: Analog output signal selection
: Inclination characteristic of analog output
: Analog output bias
Function
Output signal from the FM terminal can be switched between 0 to 1mAdc output, 0 to 20mAdc output,
and 0 to 10Vdc output with the
setting. The standard setting is 0 to 1mAdc output.
* Optional frequency meter: When using QS60T, set
=
(meter option (0 to 1mA) output).
[Parameter setting]
Title
Function
Adjustment range
Default setting
Analog output signal selection
0: Meter option (0 to 1mA)
1: Current (0 to 20mA) output
2: Voltage (0 to 10V) output
0
Inclination characteristic of analog
output
0: Negative inclination (downward slope)
1: Positive inclination (upward slope)
1
Analog output bias
-1.0 - +100.0%
0
Note: With 0 to 20mAdc (4 to 20mAdc) output, or 0 to 10Vdc output, set
to
or
.
Example of setting
=1,
=1,
=0(%)
=1,
=1,
=20(%)
0
20
(mA)
0
100%
Output current
Internal calculated value
4
20
(mA)
0
100%
f692
Output current
Internal calculated value
=1,
=0,
=100(%)
=1,
=0,
=100(%)
0
20
(mA)
0
100%
: Large gain
Output current
Internal calculated value
4
20
(mA)
0
100%
: Small gain
f692
Output current
Internal calculated value
The analog output inclination can be adjusted using the parameter
.