6.18.7 Cancel the operation command
f719
: Selection of operation command clear
Function
This parameter allows you to select operation command retained or operation command canceled,
when coast stop occurs due to standby terminal function (ST) or coast stop command terminal
function(FRR), and when under voltage in main circuit alarm(
) occurs, during panel operation or
RS485 communication operation.
Parameter setting
At coast stop
At under voltage in main circuit alarm
(
)
=
Operation command canceled
Operation command retained
=
Operation command retained
=
Operation command canceled
Operation command retained :
Inverter restarts due to canceling coast stop at coast stop.
Inverter restarts due to supply power source again when the under voltage in main circuit alarm (
)
occurs.
Operation command canceled :
Inverter doesn’t restart after coast stop or occurring the under voltage in main circuit alarm (
).
Press RUN key to operate again in panel operation.
Switch to ON the operation command in RS485 communication operation.
Title
Function
Adjustment range
Default setting
f719
Selection of operation
command clear
0: Clear at coast stop and retained at
moff
.
1: Retained at coast stop and
moff
.
2: Clear at coast stop and
moff
.
1
[Setup example of input terminal]
When it is assigned to the S1 terminal.
Title Function
Adjustment
range Setting
f113
Input terminal selection 3A
(S1)
0-201
6: ST (Standby)
f113
Input terminal selection 3A
(S1)
0-201
96: FRR (Coast stop command)
Setting value 7, 97 are reverse signa
6.18.8 Parameter registration to easy setting mode
-
: Easy setting mode parameter 1 to 24
Up to 24 arbitrary parameters can be registered to easy setting mode.
Refer to section 4.5 for details.