E6581595
H-4
8
(Continued)
Item displayed
Panel
operated
LED
display
Communic
ation No.
Description
Parts replacement
alarm information
m
}}}i
FE79
The ON/OFF status of each of the cooling fan,
circuit board capacitor, main circuit capacitor of
parts replacement alarm or cumulative operation
time are displayed in bits.
ON:
OFF:
Cumulative
operation time
FE14
The cumulative operation time is displayed.
(0.01=1 hour, 1.00=100 hours)
Default display
mode
The output frequency is displayed (Operation at
60Hz).
8.2.2
Display of detailed information on a past trip
Details on a past trip (of trips 1 to 4) can be displayed, as shown in the table below, by pressing the center of the
setting dial when the trip record is selected in the status monitor mode.
Unlike the "Display of trip information at the occurrence of a trip" in 8.3.2, details on a past trip can be displayed,
even after the inverter is turned off or reset.
Item displayed
Panel
operated
LED display
Description
Past trip 1
Past trip 1 (displayed alternately)
Continuous trips
For OCA, OCL, and Err5, the number of times (maximum of
31) the same trip occurred in succession is displayed (unit:
times). Detailed information is recorded at the beginning
and ending numbers.
Output frequency
6
The output frequency when the trip occurred is displayed.
Direction of
rotation
The direction of rotation when the trip occurred is displayed.
(
: Forward run,
: Reverse run)
Frequency
command value
The frequency command value when the trip occurred is
displayed.
Output current
The inverter output current when the trip occurred is
displayed. (%/A)
Input voltage
The inverter input voltage (DC detection) when the trip
occurred is displayed. (%/V).
(Continued overleaf)
Refer to page H-8 for notes.
Note 7
Note 8
m
}}}i
Cooling
fan
Cumulative
operation
time
Control circuit board capacitor
Main
circuit
capacitor
MODE
Note 3
Note 9
Note 2