Current reduction
According to the carrier frequency
f300
setting, you may need to reduce the inverter’s continuous
output current. Reduction rates vary depending on the capacity of the inverter.
[Three-phase/Single-phase 200 V class]
Inverter model
Ambient temperature
Input voltage 200V to 240V
PWM Carrier frequency
2 to 4 kHz
5 to 12 kHz
VFNC3-2001P
VFNC3S-2001PL
40
C or less *1
0.7 A
0.7 A
VFNC3-2002P
VFNC3S-2002PL
40
C or less *1
1.4 A
1.4 A
VFNC3-2004P
VFNC3S-2004PL
40
C or less *1
2.4 A
2.4 A
VFNC3-2007P
40
C or less *1
4.2 A
3.6 A
VFNC3S-2007PL 3.2
A
VFNC3-2015P
VFNC3S-2015PL
40
C or less *1
7.5 A
7.5 A
Above 40 to 50
C *2
7.1 A
VFNC3-2022P
40
C or less *1
10.0 A
8.5 A
VFNC3S-2022PL 9.1
A
VFNC3-2022P
VFNC3S-2022PL
Above 40 to 50
C *2
10.0 A
7.5 A
VFNC3-2037P
40
C or less *1
16.7 A
14.0 A
Above 40 to 50
C *2
[Single-phase 100 V class]
Inverter model
Ambient temperature
Input voltage 100V to 120V
PWM Carrier frequency
2 to 4 kHz
5 to 12 kHz
VFNC3S-1001P
40
C or less *1
0.7 A
0.7 A
VFNC3S-1002P
40
C or less *1
1.4 A
1.4 A
VFNC3S-1004P
40
C or less *1
2.4 A
2.4 A
VFNC3S-1007P
40
C or less *1
4.2 A
4.0 A
Above 40 to 50
C *2
*1: Maintain the ambient temperature of 40°C or less for the compliance with UL standard.
*2: Remove the protective label on the top of the inverter for the compliance with UL standard for the
ambient temperature above 40
C to 50
C.