E6581595
K-5
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0151 Input
terminal
selection 1B (F)
- -
0-201 *7
0
6.3.3
6.5.1
0152 Input
terminal
selection 2B (R)
- -
0
7.2.1
0153 Input
terminal
selection 3B (S1)
- -
0
0154 Input
terminal
selection 4B (S2)
- -
0
0155 Input
terminal
selection 1C (F)
- -
0
0156 Input
terminal
selection 2C (R)
- -
0
Basic
parameter
2
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0170
Base frequency 2
Hz
0.1/0.01
20.0-400.0
* 2
6.4.1
0171 Base
frequency
voltage 2
V 1/0.1
50-330
*
2
0172 Torque
boost
value 2
% 0.1/0.1
0.0-30.0
*
3
0173 Motor
electronic-
thermal protection
level 2
%
(A)
1/1 10-100
100 3.5
6.4.1
6.16.1
0185 Stall
prevention
level 2
%
(A)
1/1 10-199,
200 (disabled)
150 6.4.1
6.19.2
Frequency
parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0201
VI input point 1
setting
% 1/1
0-100
0 6.5.2
7.3
0202
VI input point 1
frequency
Hz 0.1/0.01
0.0-400.0
0.0
0203
VI input point 2
setting
% 1/1
0-100
100
0204
VI input point 2
frequency
Hz 0.1/0.01
0.0-400.0
*
2
0209
Analog input filter
ms
1/1
4-1000
64
0240 Starting
frequency
Hz 0.1/0.01
0.1-10.0
0.5 6.6.1
0241 Operation
starting
frequency
Hz 0.1/0.01
0.0-
0.0
6.6.2
0242 Operation
starting
frequency
hysteresis
Hz 0.1/0.01
0.0-
0.0
0249 Factory
specific
coefficient 2A
- -
-
-
*
4
*2: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*3: Default setting values vary depending on the capacity. Refer to section 11.4.
*4: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.
*7: Refer to section 11.6 for details about input terminal function.