E6581595
K-7
11
Operation
mode
parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0300 PWM
carrier
frequency
kHz
1/0.1 2
-16
12
6.11
0301 Auto-restart
control selection
- -
0:
Disabled
1: At auto-restart after momentary
stop
2: At ST terminal off and on
3: 1+2
4: At start-up
0
6.12.1
0302 Regenerative
power ride-
through control
(Deceleration
stop)
- -
0:
Disabled
1: Regenerative power ride-through
control
2: Deceleration stop during power
failure
0
6.12.2
0303 Retry
selection
(number of times)
Times
1/1 0:
Disabled
1-10
0
6.12.3
0305 Overvoltage
limit
operation
(Slowdown stop
mode selection)
- -
0:
Enabled
1: Disabled
2: Enabled (Quick deceleration
control)
3: Enabled (Dynamic quick
deceleration control)
2
6.12.4
0307 Supply
voltage
correction
(output voltage
limitation)
-
-
0: Supply voltage uncorrected,
output voltage limited
* 2
6.12.5
1: Supply voltage corrected,
output voltage limited
2: Supply voltage uncorrected,
output voltage unlimited
3: Supply voltage corrected,
output voltage unlimited
0311 Reverse-run
prohibition
-
-
0: Forward/reverse run permitted
1: Reverse run prohibited
2: Forward run prohibited
0
6.12.6
0312 Random
mode -
- 0:
Disabled
1: Automatic setting
0
6.11
0315 Factory
specific
coefficient 3A
- -
-
-
*
4
0316 Carrier
frequency
control mode
selection
-
-
0: Carrier frequency without reduction
1: Carrier frequency with automatic
reduction
1
6.11
0359 PID
control
waiting time
s 1/1
0-2400
0 6.13
0360
PID control
-
-
0: Disabled, 1: Enabled
0
0362 Proportional
gain - 0.01/0.01
0.01-100.0
0.30
0363 Integral
gain
- 0.01/0.01
0.01-100.0
0.20
0366 Differential
gain - 0.01/0.01
0.00-2.55
0.00
0380 PID
forward/reverse
characteristics
selection
- -
0:
Forward
1: Reverse
0
0391 Hysteresis
for
lower-limit
frequency
operation
Hz 0.1/0.01
0.0-
ul
0.2
6.8.1
*2: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*4: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.