E6581595
A-10
1
VFNC3S-1007P
,
2015PL
,
2022PL
P0
PA/+ PC/- U/T1 V/T2 W/T3
R/L1 S/L2/N
M4 screw
Grounding capacitor switch
(2015, 2022 PL only)
Grounding terminal
Grounding terminal
(M4 screw)
Short-circuit cover
EMC plate
for installation (Note 1)
Grounding terminal
(M4 screw)
M4 screw
Grounding
terminal
(M5 screw)
* Bend the clips on the wiring port of the terminal cover to connect the PO, PA/+, and PC/- terminals.
Note 1) The EMC plate is optional.
2) Grounding capacitor switch
Single-phase 240 V models have a built-in high-attenuation noise filter and are grounded via a capacitor.
A switch makes for easy switching to reduce leakage current from the inverter and the load on the
capacitor. However, be careful, as reducing the load means non-conformity with the EMC standard on
the inverter itself. Always do switching with the power off.
Pressing this switches the grounding capacitor's capacity from small
to large. (Default setting)
Pulling this switches the grounding capacitor's capacity from large to
small. This reduces the leakage current.
When this inverter is connected to the IT system (insulated ground
of power supply or the system has Impedance), the switch has to be
pulled as the figure shows.
Shorting-bar