E6581595
K-10
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0609 Small
current
detection
hysteresis
% 1/1
1-20
10
6.16.7
0610 Small
current
trip/alarm
selection
- -
0:
Alarm
only
1: Tripping
0
0611 Small
current
detection current
%
(A)
1/1 0-150
0
0612 Small
current
detection time
s 1/1
0-255
0
0613 Detection
of
output short-circuit
at start-up
-
-
0: Each time (standard pulse)
1: Only one time after power on
(standard pulse)
2: Each time (short pulse)
3: Only one time after power on
(short pulse)
0
6.16.8
0615 Over-torque
trip/alarm
selection
- -
0:
Alarm
only
1: Tripping
0
6.16.9
0616 Over-torque
detection level
%
1/1 0
(disabled)
1-200
150
0618 Over-torque
detection time
s 0.1/0.1
0.0-10.0
0.5
0619 Over-torque
detection
hysteresis
% 1/0.01
0-100
10
0620 Cooling
fan
ON/OFF control
-
-
0: ON/OFF control
1: Always ON
0
6.16.10
0621 Cumulative
operation time
alarm setting
100
hours
0.1/0.1
(=10 hours)
0.0-999.0 610.0
6.16.11
0627 Undervoltage
trip/alarm
selection
- -
0:
Alarm
only
(detection level 64% or less)
1: Tripping
(detection level 64% or less)
2: Alarm only
(detection level 50% or less, input
AC or DC reactor required)
0
6.16.12
0631 Factory
specific
coefficient 6A
- -
-
-
*
4
0632 Electronic-thermal
memory
- -
0:
Disabled
1: Enabled
0 3.5
6.16.1
0633 VI
analog
input
break detection
level
% 1/1
0:
Disabled,
1-100
0
6.16.13
0634 Annual
average
ambient
temperature (parts
replacement
alarms)
-
-
1: -10 to +10
C
2: 11-20
C
3: 21-30
C
4: 31-40
C
5: 41-50
C
6: 51-60
C
3
6.16.14
*4: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.