E6581595
K-16
11
11.6 Input
Terminal
Function
Table of input terminal functions 1
Function
No.
Code Function
Action
Reference
0,1 -
No
function
Disabled
-
2
F
Forward run command
ON: Forward run, OFF: Slowdown stop
3.2.1
3
FN
Inversion of forward run command
Inversion of F
7.2.1
4
R
Reverse run command
ON: Reverse run, OFF: Slowdown stop
3.2.1
5
RN
Inversion of reverse run command
Inversion of R
7.2.1
6
ST
Standby
ON: Ready for operation
OFF: Coast stop (gate OFF)
3.2.1
7
STN
Inversion of standby
Inversion of ST
8
RES
Reset command
ON: Acceptance of reset command
ON
OFF: Trip reset
13.2
9
RESN
Inversion of reset command
Inversion of RES
10
SS1
Preset-speed command 1
Selection of 15-speed SS1 to SS4 (SS1N to SS4N) (4 bits)
3.6
11
SS1N
Inversion of preset-speed command 1
7.2.1
12
SS2
Preset-speed command 2
13
SS2N
Inversion of preset-speed command 2
14
SS3
Preset-speed command 3
15
SS3N
Inversion of preset-speed command 3
16
SS4
Preset-speed command 4
3.6
17
SS4N
Inversion of preset-speed command 4
18
JOG
Jog run mode
ON: Jogging mode (fixed at 5Hz)
OFF: Jog run canceled
7.2.1
19
JOGN
Inversion of jog run mode
Inversion of JOG
20
EXT
Emergency stop by external signal
ON:
trip stop
OFF: After stopped by
f603
,
e
trip
6.16.4
21
EXTN
Inversion of emergency stop by external signal
Inversion of EXT
22
DB
DC braking command
ON: DC braking, OFF: Brake canceled
6.7.1
23
DBN
Inversion of DC braking command
Inversion of DB
24
AD2
2nd acceleration/deceleration
ON: Acceleration/deceleration 2
OFF: Acceleration/deceleration 1
6.4.1
6.15.1
25
AD2N
Inversion of 2nd acceleration/deceleration
Inversion of AD2
28
VF2
2nd V/F control mode switching
ON: 2nd V/F control mode
(V/F fixed,
,
,
,
)
OFF: 1st V/F control mode
(
setting,
,
,
,
)
6.4.1
29
VF2N
Inversion of 2nd V/F control switching
Inversion of VF2
32
OCS2
2nd stall prevention level
ON: Enabled at the value of
OFF: Enabled at the value of
6.4.1
6.16.2
33
OCS2N
Inversion of 2nd stall prevention level
Inversion of OCS2
36
PID
PID control prohibition
ON: PID control prohibited
OFF: PID control enabled
6.13
37
PIDN
Inversion of PID control prohibition
Inversion of PID
48
SCLC
Forced local from communication
Enabled during communication
ON: Local (Setting of
,
)
OFF: Communication
5.5
6.19
49
SCLCN
Inversion of forced local from communication
Inversion of SCLC
50
HD
Operation hold (hold of 3-wire operation)
ON: F (forward run), R: (reverse run) held, 3-wire operation
OFF: Slowdown stop
7.2.1
51
HDN
Inversion of operation hold (hold of 3-wire
operation)
Inversion of HD
52
IDC
PID integral/differential clear
ON: Integral/differential clear, OFF: Clear canceled
6.13
53
IDCN
Inversion of PID integral/differential clear
Inversion of IDC
54
PIDSW
PID characteristics switching
ON: Inverted characteristics of
selection
OFF: Characteristics of
selection
55
PIDSWN
Inversion of PID characteristics switching
Inversion of PIDSW