E6581595
K-17
11
Table of input terminal functions 2
Function
No.
Code Function
Action
Reference
88
UP
Frequency UP
ON: Frequency increased
OFF: Frequency increase canceled
6.5.3
89
UPN
Inversion of frequency UP
Inversion of UP
90
DWN
Frequency DOWN
ON: Frequency decreased
OFF: Frequency decrease canceled
91
DWNN
Inversion of frequency DOWN
Inversion of DWN
92
CLR
Clear frequency UP/DOWN
OFF
ON: Clear frequency UP/DOWN
93
CLRN
Inversion of clear frequency UP/DOWN
Inversion of CLR
96
FRR
Coast stop command
ON: Coast stop (Gate OFF)
OFF: Coast stop canceled
3.2.1
97
FRRN
Inversion of coast stop command
Inversion of FRR
106
FMTB
Frequency setting mode terminal board VI
ON: Terminal board (VI) enabled
OFF: Setting of
5.5
107
FMTBN
Inversion of frequency setting mode terminal
board VI
Inversion of FMTB
108
CMTB
Command mode terminal board
ON: Terminal board enabled
OFF: Setting of
109
CMTBN
Inversion of command mode terminal board
Inversion of CMTB
110
PWE
Parameter editing permission
ON: Parameter editing permitted
OFF: Setting of
6.18.1
111
PWEN
Inversion of parameter editing permission
Inversion of PWE
122
FST
Forced deceleration command
ON: Forced deceleration command (Automatic deceleration)
OFF: Forced deceleration canceled
(Note that operation is resumed when forced deceleration is
canceled)
5.3.1
123
FSTN
Inversion of forced deceleration command
Inversion of FST
200
PWP
Parameter editing prohibition
ON: Parameter editing prohibited
OFF: Setting of
6.18.1
201
PWPN
Inversion of parameter editing prohibition
Inversion of PWP
Note 1: Function No. 26, 27, 30, 31, 34, 35, 38 to 47, 50, 51, 56 to 87, 94, 95, 98 to 105, 112 to 121 and 124 to 199 are
assigned "No function".
Note 2: Function No. are different from those on the VF-nC1. Pay attention to substitute function No. from VF-nC1 to VF-nC3.
The combination function in VF-nC1 (e.g. F+SS1) can be realized by plural assignable functions (
f151
to
f156
).
As a combination is not constraint, various operation is possible. Refer to section 7.2.1 for details.