E6581595
L-1
12
12. Specifications
12.1 Models and their standard specifications
Standard specifications
Item Specification
Input voltage class
3-phase 240V class
Applicable
motor
(kW) 0.1 0.2 0.4 0.75 1.5 2.2 4.0
R
at
ing
Type VFNC3
Form
2001P 2002P 2004P 2007P 2015P 2022P 2037P
Capacity (kVA) Note 1)
0.3
0.6
1.0
1.6
2.9
3.9
6.4
Output current
(A) Note 2)
0.7
(0.7)
1.4
(1.4)
2.4
(2.4)
4.2
(3.6)
7.5
(7.5)
10.0
(8.5)
16.7
(14.0)
Output voltage Note 3)
3-phase 200V to 240V
Overload current rating
150
%
-60 seconds, 200%-0.5 second
P
ower s
uppl
y
Voltage-frequency
3-phase 200V to 240V - 50/60Hz
Allowable fluctuation
Voltage 170 to 264V Note 4), frequency ±5%
Required Power supply
capacity (kVA) Note 5)
0.5 0.8 1.4 2.5 4.3 5.7 9.2
Protective method (IEC60529)
IP20
Cooling method
Self-cooling
Forced air-cooled
Color
RAL 3002 / 7016
Built-in filter
-
Item Specification
Input voltage class
1-phase 240V class
1-phase 120V class
Applicable
motor
(kW)
0.1 0.2 0.4 0.75 1.5 2.2 0.1 0.2 0.4 0.75
R
at
ing
Type VFNC3S
Form
2001PL
2002PL
2004PL
2007PL
2015PL
2022PL
1001P 1002P 1004P 1007P
Capacity
(kVA)
Note
1)
0.3 0.6 1.0 1.6 2.9 3.9 0.3 0.6 1.0 1.6
Output current
(A) Note 2)
0.7
(0.7)
1.4
(1.4)
2.4
(2.4)
4.2
(3.2)
7.5
(7.5)
10.0
(9.1)
0.7
(0.7)
1.4
(1.4)
2.4
(2.4)
4.2
(4.0)
Rated output voltage Note 3)
3-phase 200V to 240V
3-phase 200V to 240V
Overload current rating
150
%
-60 seconds, 200% -0.5 second
150
%
-60 seconds, 200%-0.5 second
P
ower s
uppl
y
Voltage-frequency
1-phase 200V to 240V - 50/60Hz
1-phase 100V to 120V – 50/60Hz
Allowable fluctuation
Voltage 170 to 264V Note 4), frequency ±5%
Voltage 85 to 132V Note 4), frequency±5
%
Required Power supply
capacity (kVA) Note 5)
0.5 0.8 1.3 2.3 4.0 5.4 0.4 0.7 1.3 2.1
Protective method (IEC60529)
IP20
IP20
Cooling method
Self-cooling
Forced air-cooled
Self-cooling
Forced air-
cooled
Color
RAL 3002 / 7016
RAL 3002 / 7016
Built-in filter
EMC filter
-
Note 1. Capacity is calculated at 220V for output voltage.
Note 2. Indicates rated output current setting when the PWM carrier frequency (parameter
f300
) is 4kHz or less. Between 5
kHz and 12 kHz, the rated output current is indicated in the ( ). Above 13 kHz, the output current must be reduced. The
default setting of the PWM carrier frequency is 12kHz. (Refer to section 6.11)
Note 3. Maximum output voltage is the same as the input voltage. In case of 1-phase 120V class, maximum output voltage is
same as twice the input voltage.
With regard to 120V models, the output voltage may decrease about 10 to 20 % if motor load is applied. When
operating VFNC3 in conjunction with general-purpose motor (200V), it is necessary to reduce the motor load.
Note 4. 180V-264V (240V class), 90V-132V (120V class) when the inverter is used continuously (load of 100%).
Note 5. Required power supply capacity varies with the value of the power supply side inverter impedance (including those of
the input reactor and cables).