[Trip information]
Error code
Failure code
Name
Description
Remedies
0011 Emergency
stop
During automatic operation or remote
operation, an emergency stop command
is entered from the operation panel or an
external (terminal or communication).
Reset the inverter.
If the emergency stop signal is input,
reset after releasing this signal.
0012
EEPROM fault 1
The EEPROM is writing error.
Turn off the inverter, then turn it again.
If it does not recover from the error,
contact your Toshiba distributor.
0013
EEPROM fault 2
typ
operation was aborted by power
supply off etc.
Turn off the inverter, then turn it again,
and then try
typ
operation again.
The EEPROM is reading error.
Turn off the inverter, then turn it again.
If it does not recover from the error,
contact your Toshiba distributor.
0014
EEPROM fault 3
The EEPROM is defective.
Contact your Toshiba distributor.
0015
Main unit RAM fault
The control RAM is defective.
Contact your Toshiba distributor.
0016
Main unit ROM fault
The control ROM is defective.
Contact your Toshiba distributor.
0017
CPU fault 1
The control CPU is defective.
Contact your Toshiba distributor.
0018
Remote control error
The communication with external devices
was broken off.
Check the remote control device, cables,
etc.
*
001D Low-current
operation
Trip
The output current decreased to a low-
current detection level during operation.
Enable
(low-current detection).
Check the suitable detection level for the
system (
,
,
).
Contact your Toshiba distributor if the
setting is correct.
*
001E Undervoltage
trip
(main circuit)
The input voltage (in the main circuit) is
too low.
Check the input voltage.
Enable
(undervoltage trip
selection).
To take measures to momentary power
failure, set
=
or
,
Regenerative power ride-through control
f302
and Auto-restart control selection
f301
.
0022
Ground fault trip
A ground fault occurs in the output cable
or the motor.
Check the cable and the motor for ground
faults.
0028
0054
0055
0056
Auto-tuning error
The motor parameter
,
,
,
,
are not set correctly.
Set the left column parameters correctly
as a motor name plate and make an auto-
tuning again.
Set parameter
f416
to smaller 70% of
the present value, and execute the auto-
tuning again.
The motor with the capacity of 2 classes
or less than the inverter is used.
The output cable is too thin.
The inverter is used for loads other than
those of three-phase induction motors.
Set the left column parameters correctly
as a motor name plate and make an auto-
tuning again.
Then set
f400
=
1
, when trip occurs.
The motor is not connected.
Connect the motor.
Check whether the secondary magnetic
contactor.
The motor is rotating.
Make an auto-tuning again after the
rotation of the motor stops.
0029 Inverter
type
error
It may be a breakdown failure.
Contact your Toshiba distributor.
0045
Over speed fault
The input voltage fluctuates abnormally.
Over speed fault due to the overvoltage
limit operation.
Check the input voltage.
Install an optional braking module.
*
0032
Brea in analog signal
cable
The input signal from VI is equal to or less
than the
setting.
Check the VI signal cable for breaks.
Also, check the input signal value or
setting of
.
* You can select a trip ON/OFF by parameters.