E6581595
A-22
1
The space shown in the diagram is the minimum allowable space. Because air cooled equipment has cooling
fans built in on the top or bottom surfaces, make the space on top and bottom as large as possible to allow
for air passage.
Note: Do not install in any location where there is high humidity or high temperatures and where there are
large amounts of dust, metallic fragments and oil mist.
Calorific values of the inverter and the required ventilation
About 5% of the rated power of the inverter will be lost as a result of conversion from AC to DC or from DC to
AC. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the
interior of the cabinet must be ventilated and cooled.
The amount of forcible air-cooling ventilation required and the necessary heat discharge surface quantity
when operating in a sealed cabinet according to capacity are as follows.
Notes
1)
Case of 100% Load Continuation operation. The heat loss for the optional external devices (input
reactor, DC reactor, radio noise reduction filters, etc.) is not included in the calorific values.
2)
It is power consumption when power is on but output frequency is 0Hz, and cooling fan is activated.
Voltage class
Inverter type
Calorific values
Note 1)
Amount of forcible air
cooling ventilation
required (m
3
/min)
Heat discharge surface
area required for sealed
storage cabinet (m
3
)
Standby power
requirement
(W)
Note 2)
4kHz 12kHz 4kHz 12kHz 4kHz 12kHz
Three-phase
240V class
VFNC3-
2001P
2002P
2004P
2007P
2015P
2022P
2037P
13
16
24
41
73
85
128
14
18
28
45
85
90
133
0.07
0.09
0.14
0.23
0.41
0.48
0.73
0.08
0.10
0.16
0.26
0.48
0.51
0.75
0.26
0.32
0.48
0.82
1.46
1.70
2.56
0.28
0.36
0.56
0.90
1.70
1.80
2.66
8
8
8
8
12
12
12
Single-phase
240V class
VFNC3S-
2001PL
2002PL
2004PL
2007PL
2015PL
2022PL
13
18
27
44
72
93
14
20
31
43
83
102
0.07
0.10
0.15
0.25
0.41
0.53
0.08
0.11
0.18
0.24
0.47
0.53
0.26
0.36
0.54
0.88
1.44
1.86
0.28
0.40
0.62
0.86
1.66
2.04
8
8
8
8
11
11
Single-phase
120V class
VFNC3S-
1001P
1002P
1004P
1007P
13
18
29
48
14
20
33
54
0.07
0.10
0.16
0.27
0.08
0.11
0.19
0.31
0.26
0.36
0.58
0.96
0.28
0.40
0.66
1.08
8
8
8
11