E6581595
B-9
2
Terminal
symbol
Input /
output
Function
Electrical
specifications
Inverter internal circuits
OUT
NO
Output
Multifunction programmable open
collector output. Standard default setting
detect and output low speed signal.
Multifunction output terminals to which
two different functions can be assigned.
The NO terminal is an isoelectric output
terminal. It is insulated from the CC
terminal.
By changing parameter settings, these
terminals can also be used as
multifunction programmable pulse train
output terminals.
Open collector output
24Vdc-100mA
To output pulse
trains,
a current of 10mA
or more needs to
be passed.
Pulse frequency
range:
38
~
1600pps
OUT
NO
10
FLA
FLB
FLC
Note 2)
Output
Multifunction programmable relay contact
output.
Detects the operation of the inverter's
protection function.
Contact across FLA-FLC is closed and FLB-
FLC is opened during protection function
operation.
Max. switching
capacity
250Vac-2A
30Vdc-2A
(cos
=1)
: at resistive load
250Vac-1A
(cos
=0.4)
30Vdc-1A
(L/R=7ms)
Min. permissible
load
5Vdc-100mA
24Vdc-5mA
FLA
FLC
FLB
RY
+24V
Note 2) A chattering (momentary ON/OFF of contact) is generated by external factors of the vibration and the impact, etc. In
particular, please set the filter of 10ms or more, or timer for measures when connecting it directly with input unit terminal
of programmable controller. Please use the OUT terminal as much as possible when the programmable controller is
connected.