E6581595
E-13
5
5.6
Meter setting and adjustment
: Meter selection
: Meter adjustment gain
Refer to section 3.4 for details.
5.7
Forward/reverse run selection (Panel keypad)
: Forward/reverse run selection (Panel keypad)
Function
Program the direction of rotation of the motor when the running and stopping are made using the RUN
key and STOP key on the operation panel.
Valid when
(command mode) is set to
(operation panel).
[Parameter setting]
Title
Function
Adjustment range
Default setting
Forward/reverse run selection
(Panel keypad)
0: Forward run
1: Reverse run
2: Forward run (F/R switching on
extension panel)
3: Reverse run (F/R switching on
extension panel)
0
Using extension panel RKP007Z (option) : When
is set to
and the standard monitor is displayed,
pressing the FWD/REV key changes the direction of rotation from forward to reverse after displaying the
message
.
Pressing the FWD/REV key again changes the direction of rotation from reverse to forward after displaying
the message
.
Using extension panel RKP002Z (option) : When
is set to
and the standard monitor is displayed,
pressing the DOWN key while pressing the ENT key changes the direction of rotation from forward to
reverse after displaying the message
.
Pressing the UP key while pressing the ENT key again changes the direction of rotation from reverse to
forward after displaying the message
.
Check the direction of rotation on the status monitor. Refer to section 8.1 for details about monitor.
: Forward run
: Reverse run
When the F and R terminals are used for switching between forward and reverse rotation from the terminal
board, the
forward/reverse run selection parameter is rendered invalid.
Short across the F-CC terminals: forward rotation
Short across the R-CC terminals: reverse rotation.