E6582233
F-1
6
6. Other parameters
Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes. Modify
parameter settings as required. Refer to section 10 tables of extended parameters.
6.1 Input/output
parameters
6.1.1 Low-speed
signal
: Low-speed signal output frequency
Function
When the output frequency exceeds the setting of
an ON signal will be generated. This signal
can be used as an electromagnetic brake excitation/release signal.
This signal can also be used as an operation signal when
is set to 0.0Hz, because an ON
signal is put out if the output frequency exceeds 0.0Hz.
Output from the open collector output terminal OUT. (Default)
Output from relay output FLA-FLB-FLC is possible depending on the parameter settings.
[Parameter setting]
Title Function
Adjustment range
Default setting
Low-speed signal output frequency
0.0 -
(Hz)
0.0
Output frequency
Time [s]
Low-speed detection signal :
OUT-NO terminals
ON
OFF
Inversion of low-speed
detection signal
ON
OFF
[Hz]
0
Setting frequency