[If momentary power failure occurs]
An example of setting when
f302
=
2
• Even after the recovery from an input power failure, the motor continues deceleration stop. If the DC voltage falls
below a certain level, however, control will be stopped and the motor will coast.
• If the voltage in main circuit falls below main circuit undervoltage (
moff
) level at operation deceleration stop
during power failure, the motor will coast and inverter displays
stop
and
0.0
alternately. The motor continues
coasting even after power supply is restored.
Motor speed
Input voltage
Note 3: If momentary power failure occurs during deceleration stop,
power ride-through control will not be performed.
DC Voltage
Normal acceleration
Motor speed
Time
Input voltage
Deceleration stop