E6582233
F-31
6
[Parameter setting]
Title Function
Setting
f304
Dynamic braking selection
1
f305
Overvoltage limit operation
1
f308
Dynamic braking resistance
Proper value
f309
Dynamic braking resistor capacity
Proper value
f626
Over-voltage stall protection level
136 (%)
★
To use this inverter in applications that create a continuously regenerative status (such as downward
movement of a lift, a press or a tension control machine), or in applications that require deceleration
stopping of a machine with a significant load inertial moment, increase the dynamic braking resistor
capacity according to the operation rate required.
★
To connect an external dynamic braking resistor, select one with a resultant resistance value greater than
the minimum allowable resistance value. Be sure to set the appropriate operation rate in
f308
and
f309
to ensure overload protection.
★
When using a braking resistor with no thermal fuse, connect and use a thermal relay as a control circuit for
cutting power off.