E6582233
F-38
6
[Parameter setting]
Title Function
Adjustment range
Default setting
PID control waiting time
0-2400 [s]
0
PID control
0: Disabled, 1: Enabled
0
Proportional
gain
0.01-100.0
0.30
Integral
gain
0.01-100.0
0.20
Differential
gain
0.00-2.55
0.00
PID forward/reverse characteristics
selection
0: Forward
1: Reverse
0
1) External connection
2) Types of PID control interfaces
Set process amount input value (frequency setting) for when doing PID control.
Process amount input value (frequency setting) Feedback
signal
Frequency setup mode selection:
1: Setting dial 1 (press in center to save)
2: Setting dial 2 (save even if power is off)
3: RS485 communication
5: UP/DOWN from external logic input
External analog input
VI (DC: 4 - 20mA/
DC: 0 - 10V/
DC: 0 - 5V)
Preset-speed operation (
,
are all possible)
Note 1: Regarding setting value for
: Terminal VI is used for a feed back signal, do not set
(terminal VI).
M
P
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
VI
CC
Pressure
transmitter
(1) Panel setting
(2) Internal preset-speed
setting
Feedback signals (1)DC : 4~20mA (2)DC : 0~10V (3)DC : 0~5V
(1) Panel keypad setting