Applied operations by an I/O signal (operation from
the terminal block)
7.2.1
Input terminal function
This function is used to send a signal to the input terminal from an external programmable controller to operate or
configure the inverter.
The ability to select from a variety of functions allows for flexible system design.
[Control terminal board]
OUT NO CC F
R S1 S2 P24
FLA FLB FLC
CC VI P5 FM
Settings for the logic input terminal function
Terminal
symbol
Title
Function
Adjustment range
Default setting
F
Input terminal selection 1A (F)
0-201 Note 1)
2 (F)
Input terminal selection 1B (F)
0 (No function)
Input terminal selection 1C (F)
0 (No function)
R
Input terminal selection 2A (R)
0-201 Note 1)
4 (R)
Input terminal selection 2B (R)
0 (No function)
Input terminal selection 2C (R)
0 (No function)
S1
Input terminal selection 3A (S1)
0-201 Note 1)
10 (SS1)
Input terminal selection 3B (S1)
0 (No function)
S2
Input terminal selection 4A (S2)
0-201 Note 1)
12 (SS2)
Input terminal selection 4B (S2)
0 (No function)
VI
Analog/logic input
Selection (VI terminal)
0: Voltage signal input (0 - 10 V)
1: Current signal input (4 - 20 mA)
2: Logic input
3: Voltage signal input (0 - 5 V)
0
Input terminal selection 5 (VI)
8-55 Note 3) 14
(SS3)
Note 1) Multiple functions assigned to a single terminal operate simultaneously.
Note 2) In case of setting always active function, assign the menu number to
and
(always active
function selection).
Note 3) When VI is used for the logic input, always connect a resistor between VI and terminal P24 in sink logic,
between VI and terminal CC in source logic. Refer to section
2.3.2 (page B-12) for details.