E6582233
J-3
10
Title
Communicati
on No.
Function Unit
Minimum
setting unit
Panel/Comm
unication
Adjustment range
Default
setting
User
setting
Reference
OLM
0017 Electronic-thermal
protection
characteristic
selection
- -
Setting
Overload
protection
OL
stall
0 3.4
0
Standard
motor
valid invalid
1 valid
valid
2 invalid
invalid
3 invalid
valid
4
VF motor
valid invalid
5 valid
valid
6 invalid
invalid
7 invalid
valid
SR1 0018
Preset-speed
frequency 1
Hz 0.1/0.01
-
0.0
3.5
SR2 0019
Preset-speed
frequency 2
Hz
0.1/0.01
-
0.0
SR3 0020
Preset-speed
frequency 3
Hz 0.1/0.01
-
0.0
SR4 0021
Preset-speed
frequency 4
Hz 0.1/0.01
-
0.0
SR5
0022 Preset-speed
frequency 5
Hz
0.1/0.01
-
0.0
SR6 0023
Preset-speed
frequency 6
Hz 0.1/0.01
-
0.0
SR7 0024
Preset-speed
frequency 7
Hz 0.1/0.01
-
0.0
TYP
0007
Default setting
-
-
0: -
1: 50Hz default setting
2: 60Hz default setting
3: Default setting 1 (Initialization)
4: Trip record clear
5: Cumulative operation time clear
6: Initialization of type information
7: Save user setting parameters
8. Load user setting parameters
9. Cumulative fan operation time
record clears
10 to 11: -
12: Number of starting clear
0
4.3
4.3.2
PSEL
0050 Registered
parameters display
selection
-
-
0: Standard setting mode at power on
1: Easy setting mode at power on
2: Easy setting mode only
0
4.4
F1-- -
Extended parameter
starting at 100
- -
-
- - 4.2.2
F2--
-
Extended parameter
starting at 200
-
-
-
-
-
F3-- -
Extended parameter
starting at 300
- -
-
- -
F4-- -
Extended parameter
starting at 400
- -
-
- -
F5--
-
Extended parameter
starting at 500
-
-
-
-
-
F6-- -
Extended parameter
starting at 600
- -
-
- -
F7-- -
Extended parameter
starting at 700
- -
-
- -
F8--
-
Extended parameter
starting at 800
-
-
-
-
-
GRU
- Automatic
edit
function
- -
-
-
-
4.3.1