E6582233
J-7
10
Title
Communicati
on No.
Function Unit
Minimum
setting unit
Panel/Comm
unication
Adjustment range
Default
setting
User
setting
Reference
F292
0292 Preset-speed
frequency 13
Hz 0.1/0.01
0.0 3.5
6.11
F293
0293 Preset-speed
frequency 14
Hz 0.1/0.01
0.0
F294
0294
Preset-speed
frequency 15
Hz 0.1/0.01
0.0
Operation mode parameters
Title
Communicati
on No.
Function Unit
Minimum
setting unit
Panel/Comm
unication
Adjustment range
Default
setting
User
setting
Reference
F300
0300 PWM
carrier
frequency
kHz
1/0.1
2 -12 (Over 4kHz is available at
f316
=0,1)
4 6.12
F301
0301 Auto-restart
control selection
- -
0:
Disabled
1: At auto-restart after momentary
stop
2: At ST terminal off and on
3: 1+2
4: At start-up
0
6.13.1
F302
0302 Regenerative
power ride-
through control
(Deceleration
stop)
- -
0:
Disabled
1: Regenerative power ride-through
control
2: Deceleration stop during power
failure
0
6.13.2
F303
0303 Retry
selection
(number of times)
Time
s
1/1 0:
Disabled
1-10
0
6.13.3
F304
0304 Dynamic
braking
selection
- -
0:
Disabled
1: Enabled, Resistor overload
protection enabled
2: Enabled
3: Enabled, Resistor overload
protection enabled
(At ST terminal on)
4: Enabled (At ST terminal on)
0
6.13.4
F305
0305 Overvoltage
limit
operation
(Slowdown stop
mode selection)
- -
0:
Enabled
1: Disabled
2: Enabled (Quick deceleration
control)
3: Enabled (Dynamic quick
deceleration control)
2
6.13.5
F307
0307 Supply
voltage
correction
(output voltage
limitation)
-
-
0: Supply voltage uncorrected,
output voltage limited
2
6.13.6
1: Supply voltage corrected,
output voltage limited
2: Supply voltage uncorrected,
output voltage unlimited
3: Supply voltage corrected,
output voltage unlimited
F308
0308 Dynamic
braking
resistance
Ω
0.1/0.1
1.0-1000
*1 6.13.4
F309
0309 Dynamic
braking
resistor capacity
kW 0.01/0.01
0.01-30.00
*1
F310
0310 Factory
specific
coefficient 3A
- -
-
-
*
2
*1: Default setting values vary depending on the capacity. Refer to section 10.4.
*2: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.