E6582233
J-16
10
10.4 Default settings by inverter rating
Inverter type
Torque
boost value
Dynamic
braking
resistance
Dynamic
braking
resistor
capacity
Automatic
torque
boost value
Motor rated
capacity
Motor rated
current
Motor
no-load
current
Integrating
wattmeter
display unit
selection
/
(%)
(
Ω
)
Note 1
(kW)
Note 1
(%)
(kW)
(A)
(%)
VFNC3E-4004P 6.0
200.0
0.12
6.2
0.40
1.0
65 0
VFNC3E-4007P 6.0
200.0
0.12
5.8
0.75
1.7
60 0
VFNC3E-4015P 6.0
200.0
0.12
4.3
1.50
2.4
55 0
VFNC3E-4022P 5.0
200.0
0.12
4.1
2.20
4.5
52 0
VFNC3E-4037P 5.0
160.0
0.12
3.4
3.70
7.4
48 1
VFNC3E-4055P 4.0 80.0 0.24 2.6 5.50 10.5 46 1
VFNC3E-4075P 3.0 60.0 0.44 2.3 7.50 14.1 43 1
VFNC3E-4110P 2.0 40.0 0.66 2.2 11.00 20.3 41 1
Note 1: Refer to Note 4 in 2) Optional dynamic braking resistors of section 6.13.4 for the parameter setting of
f308
and
f309
.