E6582233
L-1
12
12. Before Contacting your Toshiba distributor
- Trip information and remedies
12.1 Trip causes/warnings and remedies
When a problem arises, diagnose it in accordance with the following table.
If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the
table, contact your Toshiba distributor.
[Trip information]
Error code
Failure
code
Problem Possible
causes
Remedies
E 0011
Emergency
stop
During automatic operation or remote
operation, a stop command is entered
from the operation panel or a remote
input device.
Reset the inverter.
If the emergency stop signal is input, reset
after releasing this signal.
E-13
0045
Over speed fault
The input voltage fluctuates abnormally.
Over speed fault due to the overvoltage
limit operation.
Check the input voltage.
Install an optional braking module.
*
E-18
0032
Brea in analog signal
cable
The input signal from VI is equal to or
less than the
setting.
Check the VI signal cable for breaks. Also, check
the input signal value or setting of
.
E-19 0033
CPU
communications
error
A communications error occurs between
control CPUs.
Contact your
Toshiba
distributor.
E-20 0034
Excessive
torque
boosted
The automatic torque boost parameter
setting is too high.
The motor has too small impedance.
Set a lower automatic torque boost
parameter
setting.
Make an auto-tuning.
E-21
0035
CPU fault 2
The control CPU is defective.
Contact your
Toshiba
distributor.
E-26
003A
CPU fault 3
The control CPU is defective.
Contact your
Toshiba
distributor.
EEP1
0012
EEPROM fault 1
The EEPROM is writing error.
Turn off the inverter, then turn it again. If it
does not recover from the error, contact
your Toshiba distributor.
EEP2
0013
EEPROM fault 2
typ
operation was aborted by power
supply off etc.
The EEPROM is reading error.
Turn the power off temporarily and turn it
back on, and then try
operation
again.
Write the data again. Contact your Toshiba
distributor when it happening frequently.
EEP3
0014
EEPROM fault 3
The EEPROM is defective.
Turn off the inverter, then turn it again. If it
does not recover from the error, contact
your Toshiba distributor.
EF2
0022
Ground fault trip
A ground fault occurs in the output cable
or the motor.
Check the cable and the motor for ground
faults.
*
EPHI 0008
Input
phase
failure
A phase failure occured in the input line
of the main circuit.
The capacitor in the main circuit lacks
capacitance.
Check the main circuit input line for phase
failure.
Set input phase failure detection selection
f608
=
0
.
Check the capacitor in the main circuit for
exhaustion.
*
EPHO
0009 Output
phase
failure
A phase failure occurred in the output
line of the main circuit.
Check the main circuit output line, motor,
etc. for phase failure.
Set output phase failure detection
selection
f605
=
0
.
ERR2
0015
Main unit RAM fault
The control RAM is defective.
Contact your
Toshiba
distributor.
ERR3
0016
Main unit ROM fault
The control ROM is defective.
Contact your
Toshiba
distributor.
ERR4
0017
CPU fault 1
The control CPU is defective.
Contact your
Toshiba
distributor.
ERR5
0018
Remote control error
The communication was broken off.
Check the remote control device, cables, etc.
* You can select a trip ON/OFF by parameters.
(Continued overleaf)