The space shown in the diagram is the minimum allowable space. Because air cooled equipment has cooling
fans built in on the top or bottom surfaces, make the space on top and bottom as large as possible to allow
for air passage.
Note: Do not install in any location where there is high humidity or high temperatures and where there are
large amounts of dust, metallic fragments and oil mist.
Calorific values of the inverter and the required ventilation
About 5% of the rated power of the inverter will be lost as a result of conversion from AC to DC or from DC to
AC. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the
interior of the cabinet must be ventilated and cooled.
The amount of forcible air-cooling ventilation required and the necessary heat discharge surface quantity
when operating in a sealed cabinet according to motor capacity are as follows.
Voltage class
Inverter type
Calorific values
Amount of forcible air
cooling ventilation
required (m
3
/min)
Heat discharge surface
area required for sealed
storage cabinet (m
3
)
Standby power
requirement
(W)
*1
4kHz 12kHz 4kHz 12kHz 4kHz 12kHz
Three-phase
400V class
VFNC3E
4004P
4007P
4015P
4022P
4037P
4055P
4075P
4110P
20
28
51
64
106
139
195
270
23
27
67
74
140
156
264
288
0.11
0.16
0.29
0.37
0.60
0.79
1.11
1.53
0.13
0.16
0.38
0.42
0.79
0.89
1.50
1.64
0.39
0.56
1.01
1.29
2.12
2.78
3.91
5.41
0.47
0.55
1.34
1.47
2.79
3.13
5.28
5.77
8
8
10
10
12
13
21
23
*1 It is power consumption when power is on but is not output (0Hz), and cooling fan is activated.
Note1) Case of 100% Load Continuation operation. The heat loss for the optional external devices (input
reactor, radio noise reduction filters, etc.) is not included in the calorific values in the table.