E6582233
7
I
When operation by using remote keypad is selected
Warning
Reference
section
Mandatory
action
Set the parameter Communication time-out time (
f803
) and Communication time-out
action (
f804
).
If these are not properly set, the inverter can not be stopped immediately in breaking
communication and this could result in injury and accidents.
An emergency stop device and the interlock that fit with system specifications must be
installed.
If these are not properly installed, the inverter can not be stopped immediately and this
could result in injury and accidents.
6.21
6.21
When sequence for restart after a momentary failure is selected (inverter)
Caution
Reference
section
Mandatory
action
Stand clear of motors and mechanical equipment.
If the motor stops due to a momentary power failure, the equipment will start suddenly
after power recovers. This could result in unexpected injury.
Attach caution label about sudden restart after a momentary power failure on inverters,
motors and equipment for prevention of accidents in advance.
6.13.1
6.13.1
When retry function is selected (inverter)
Caution
Reference
section
Mandatory
action
Stand clear of motors and equipment.
If the motor and equipment stop when the alarm is given, selection of the retry function will
restart them suddenly after the specified time has elapsed. This could result in unexpected
injury.
Attach caution label about sudden restart in retry function on inverters, motors and
equipment for prevention of accidents in advance.
6.13.3
6.13.3
Maintenance and inspection
Warning
Reference
section
Prohibited
Do not replace parts.
This could be a cause of electric shock, fire and bodily injury. To replace parts, call your
Toshiba distributor.
13.2
Mandatory
action
The equipment must be inspected every day.
If the equipment is not inspected and maintained, errors and malfunctions may not be
discovered and that could result in accidents.
Before inspection, perform the following steps.
(1) Turn off all input power to the inverter.
(2) Wait at least 15 minutes and check to make sure that the charge lamp is no longer lit.
If inspection is performed without performing these steps first, it could lead to electric
shock.
13.
13.
13.2